Loading...
3 Mounting and Commissioning
254
7UM61 Manual
C53000-G1176-C127-3
Figure 3-12 Installing a 7UM612 in a rack or cubicle (housing size 1/2)
3.1.3.3 Panel Surface Mounting
For installation proceed as follows:
Secure the device to the panel with four screws. For dimensions see for the Tech-
nical Data in Section 4.26.
Connect the ground of the device to the protective ground of the panel. The cross-
sectional area of the ground wire must be equal to the cross-sectional area of any
other control conductor connected to the device. The cross-section of the ground
wire must be at least 2.5 mm
2
.
Connect solid, low-impedance operational grounding (cross-sectional area = 2.5
mm
2
) to the grounding surface on the side. Use at least one M4 screw for the device
ground.
Connect the threaded terminals on the top and bottom of the device according to
the elementary diagram for the panel. The SIPROTEC
®
4 System Description has
pertinent information regarding wire size, lugs, bending radii, etc.
www . ElectricalPartManuals . com