2.36 Command Processing
223
7UM61 Manual
C53000-G1176-C127-3
2.36.3.1 Functional Description
Checking a
Command Job
Please observe the following:
Command entry, e.g. using the integrated operator interface
Check password access rights
Check switching mode (interlocked/non-interlocked) selection of de-interlock-
ing status.
User-Configurable Command Checks
Switching authority
Device Direction Check (scheduled vs. actual comparison)
Interlocking, Bay Interlocking (logic using CFC)
Interlocking, System Interlocking (centrally, using SICAM)
Double Operation Locking (interlocking against parallel switching operations)
Protection Blocking (blocking of switching operations by protective functions)
fixed command checks
Timeout Monitoring (time between initiation of the command and its completion).
Configuration in Process (if configuration is in process, commands are rejected
or delayed)
Equipment available as output (if a resource was configured, but not allocated to
a binary input, the command is rejected)
Output Blocking (if output blocking has set object-specifically and the command
is currently active, then the command is rejected)
Module hardware error
Command for this resource already active (only one command can be processed
at a time for a resource, object-related Double Operation Block)
1–of–n check (for multiple allocations such as common contact relays, whether
a command procedure was already initiated for the output relays concerned is
checked).
Command execu-
tion monitoring
The following is monitored:
Interruption of a command procedure because of a Cancel Command
Run Time Monitor (feedback indication monitoring time)