EasyManua.ls Logo

Siemens Siprotec 7UM612 - Page 196

Siemens Siprotec 7UM612
424 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Functions
196
7UM61 Manual
C53000-G1176-C127-3
9034 RTD 3 STAGE 1 -58 .. 482 °F; 212 °F RTD 3: Temperature Stage 1
Pickup
9035 RTD 3 STAGE 2 -50 .. 250 °C; 120 °C RTD 3: Temperature Stage 2
Pickup
9036 RTD 3 STAGE 2 -58 .. 482 °F; 248 °F RTD 3: Temperature Stage 2
Pickup
9041A RTD 4 TYPE Not connected
Pt 100
Ni 120
Ni 100
Not connected RTD 4: Type
9042A RTD 4 LOCATION Oil
Ambient
Winding
Bearing
Other
Other RTD 4: Location
9043 RTD 4 STAGE 1 -50 .. 250 °C; 100 °C RTD 4: Temperature Stage 1
Pickup
9044 RTD 4 STAGE 1 -58 .. 482 °F; 212 °F RTD 4: Temperature Stage 1
Pickup
9045 RTD 4 STAGE 2 -50 .. 250 °C; 120 °C RTD 4: Temperature Stage 2
Pickup
9046 RTD 4 STAGE 2 -58 .. 482 °F; 248 °F RTD 4: Temperature Stage 2
Pickup
9051A RTD 5 TYPE Not connected
Pt 100
Ni 120
Ni 100
Not connected RTD 5: Type
9052A RTD 5 LOCATION Oil
Ambient
Winding
Bearing
Other
Other RTD 5: Location
9053 RTD 5 STAGE 1 -50 .. 250 °C; 100 °C RTD 5: Temperature Stage 1
Pickup
9054 RTD 5 STAGE 1 -58 .. 482 °F; 212 °F RTD 5: Temperature Stage 1
Pickup
9055 RTD 5 STAGE 2 -50 .. 250 °C; 120 °C RTD 5: Temperature Stage 2
Pickup
9056 RTD 5 STAGE 2 -58 .. 482 °F; 248 °F RTD 5: Temperature Stage 2
Pickup
9061A RTD 6 TYPE Not connected
Pt 100
Ni 120
Ni 100
Not connected RTD 6: Type
9062A RTD 6 LOCATION Oil
Ambient
Winding
Bearing
Other
Other RTD 6: Location
Addr. Parameter Setting Options Default Setting Comments
www . ElectricalPartManuals . com

Table of Contents

Related product manuals