1 Introduction
24
7UM61 Manual
C53000-G1176-C127-3
Negative Sequence
Protection
Precise evaluation of negative sequence component of the three phase currents.
Alarm stage when a set unbalanced load is exceeded.
Thermal characteristic with adjustable negative sequence factor and adjustable
cooldown time.
High-speed trip stage for large unbalanced loads (can be used for short-circuit pro-
tection).
Underexcitation
protection
Conductance measurement from positive sequence components.
Multi-step characteristic for steady-state and dynamic stability limits;
Consideration of excitation voltage (only via binary input).
Reverse Power Pro-
tection
Calculation of power from positive sequence components.
Highly sensitive and precise active power measurement (detection of small motor-
ing powers even with low power factor cos ϕ , angle error compensation).
Insensitive to power fluctuations.
Long-time stage and short-time stage (active with closed emergency tripping valve).
Forward Power Su-
pervision
Calculation of power from positive sequence components.
Supervision of over-power (P>) and/or under-power (P<) of active power output
with individually adjustable power limits.
Optionally high-speed or high-accuracy measurement.
Impedance protec-
tion
Overcurrent pickup with undervoltage seal-in (for synchronous machines which
take their excitation voltage from the terminals).
2 impedance zones, 1 overreach zone (switchable via binary input), 4 time stages.
Polygonal tripping characteristics;
Undervoltage Pro-
tection
Two-stage undervoltage measurement of positive sequence component of voltag-
es.
Overvoltage Pro-
tection
Two-stage overvoltage measurement of the highest of the three voltages.
Optionally with phase-to-phase voltages or phase-to-earth voltages.
Frequency Protec-
tion
Monitoring on undershooting (f<) and/or overshooting (f>) with 4 frequency limits
and delay times that are independently adjustable.
Insensitive to harmonics and abrupt phase angle changes.
Settable undervoltage threshold.
Overexcitation Pro-
tection
Calculation of the ratio U/f.
Adjustable warning and tripping stage.
Standard characteristic or arbitrary trip characteristic for calculation of the thermal
stress, selectable.