4 Technical Data
302
7UM61 Manual
C53000-G1176-C127-3
EMC Tests for Interference Immunity (type tests)
EMC Tests For Noise Emission (type test)
Standards: IEC 60,255-6 and -22 (product standards)
EN 50,082-2 (Generic standard)
DIN VDE 0435-110
High Frequency Test
IEC 60,255-22-1, Class III
and VDE 0435 Part 303, Class III
2.5 kV (Peak); 1 MHz; τ = 15 µs; 400 surges per
s; Test duration 2 s; R
i
= 200 Ω
Electrostatic Discharge
IEC 60,255-22-2, Class IV
and IEC 61,000-4-2, Class IV
8 kV contact discharge; 15 kV air discharge, both
polarities; 150 pF; R
i
= 330 Ω
Irradiation with HF field, frequency sweep
IEC 60,255-22-3, Class III
IEC 61,000-4-3, Class III
10 V/m: 80 MHz to 1000 MHz,
10 V/m: 800 MHz to 960 MHz,
20 V/m: 1.4 GHz to 2.0 GHz,
80 % AM; 1 kHz,
Irradiation with HF field, single frequencies
IEC 60,255-22-3, IEC 61,000-4-3
– amplitude-modulated
– pulse-modulated
Class III: 10 V/m;
80/160/450/900 MHz; 80 % AM; 1 kHz, duty
cycle > 10 s
900 MHz; 50 % PM, repetition frequency 200 Hz
Fast Transient Disturbance Variables / Burst
IEC 60,255-22-4 and IEC 61,000-4-4, Class
IV
4 kV; 5/50 ns; 5 kHz; Burst length = 15 ms; repe-
tition rate 300 ms; both polarities: R
i
= 50 Ω; Test
duration 1 min
High energy impulse voltages (SURGE),
IEC 61 000-4-5 Installation class 3
Impulse: 1.2/50 µs
Auxiliary Voltage common mode: 2 kV; 12 Ω; 9 µF
diff. mode:1 kV; 2 Ω; 18 µF
Measuring Inputs, Binary Inputs,
Relay Outputs
common mode: 2 kV; 42 Ω; 0.5 µF
diff. mode: 1 kV; 42 Ω; 0.5 µF
Line conducted HF, amplitude modulated
IEC 61 000-4-6, Class III
10 V; 150 kHz to 80 MHz; 80 % AM; 1 kHz
Power System Frequency Magnetic Field
IEC 61,000-4-8, Class IV
IEC 60,255-6
30 A/m continuous; 300 A/m for 3 s; 50 Hz,
0.5 mT; 50 Hz
Oscillatory Surge Withstand Capability
IEEE C37.90.1
2.5 kV (peak value); 1 MHz; τ = 15 µs, 400 surges
per s; Test Duration 2 s; R
i
= 200 Ω
Fast Transient Surge Withstand Cap. IEEE
C37.90.1
4 kV; 5/50 ns; 5 kHz; burst length 15 ms; repeti-
tion rate 300 ms;both polarities, R
i
= 50 Ω; test
duration 1 min
Radiated Electromagnetic Interference IEEE
Std C37.90.2
35 V/m: 25 MHz to 1000 MHz
Damped Oscillations
IEC 60,694, IEC 61,000-4-12
2.5 kV (Peak Value), polarity alternating 100 kHz,
1 MHz, 10 MHz and 50 MHz, R
i
= 200 Ω
Standard: EN 50,081-* (technical generic standard)
Radio Noise Voltage to Lines, Only Power
Supply Voltage IEC-CISPR 22
150 kHz to 30 MHz
Limit Class B
Radio Noise Field Strength IEC-CISPR 11 30 MHz to 1000 MHz Limit Class B
www . ElectricalPartManuals . com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Siprotec 7UM612 and is the answer not in the manual?

Siemens Siprotec 7UM612 Specifications

General IconGeneral
BrandSiemens
ModelSiprotec 7UM612
CategoryRelays
LanguageEnglish

Related product manuals