4.2 Definite-Time Overcurrent Protection (I>, ANSI 50/51; I>>, ANSI 50/51/67)
307
7UM61 Manual
C53000-G1176-C127-3
Influencing Variables for Pickup Values
Auxiliary direct voltage in range 0.8
U
A
/U
AN
1.15
1 %
Temperature in Range
23°F or –5 °C Θ
amb
131°F or 55 °C
0.5 % / 10 K
Frequency in Range 0.95 f/f
N
1.05 1 %
Harmonics
– Up to 10 % 3rd harmonic
– Up to 10 % 5th harmonic
1 %
1 %