EasyManuals Logo

Siemens SIPROTEC User Manual

Siemens SIPROTEC
776 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #229 background imageLoading...
Page #229 background image
Functions
2.8 Earth Fault Protection in Earthed Systems (optional)
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
229
Determination of direction with compensated zero-sequence power
The zero-sequence power may also be used for direction determination. In this case the sign of the compen-
sated zero-sequence power is decisive. This is the zero-sequence power component S
r
as mentioned above
under „Zero-Sequence Power“ in direction of a configurable compensation angle ϕ
comp
, i.e.
S
r
=3I
0
·3U
0
·cos(ϕ – ϕ
Comp
).
The direction determination yields
• forward if S
r
is positive and S
r
> S FORWARD,
• reverse if S
r
is negative and |S
r
| > S FORWARD,
The determination of direction requires a minimum current 3I
0
and a minimum displacement voltage which can
be set as 3U0>. The prerequisite is still that the compensated zero-sequence power has a configurable
minimum magnitude. Direction determination is also blocked if the device detects a fault condition in the voltage
transformer secondary circuit (binary input reports trip of the voltage transformer mcb, „Fuse Failure Monitor“,
measured voltage failure monitoring) or a single-pole dead time. Figure 2-112 shows an example of the direc-
tional characteristic.
Figure 2-112 Directional characteristic with zero sequence power, example S
r
= setting value S FORWARD
Selection of the earth faulted phase
Since the earth fault protection uses the quantities of the zero-sequence system and the negative sequence
system, the faulted phase cannot be determined directly. To enable single-pole automatic reclosure in case of
high-resistance earth faults, the earth fault protective function features a phase selector. The phase-selector
detects by means of the distribution of the currents and voltages whether a fault is single-phase or multi-phase.
If the fault is single-phase, the faulted phase is selected. The phase selector is blocked during a single-pole
automatic reclosure.
Once a multi-phase fault has been detected, a three-pole trip command is generated. Three-pole tripping is
also initiated if single-pole tripping would be possible but is not permitted. Single-pole tripping is prevented by
the setting or three-pole coupling of other internal protection functions or of an external reclosing device via
binary input.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC and is the answer not in the manual?

Siemens SIPROTEC Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC
CategoryProtection Device
LanguageEnglish

Related product manuals