EasyManua.ls Logo

Siemens SIPROTEC

Siemens SIPROTEC
776 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Introduction
1.3 Characteristics
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
29
Phase segregated tripping possible (for operation with single-pole or single-and three-pole auto-reclosure)
(order variant)
Distance Protection (optional)
Can be used either to operate in parallel to differential protection, or as the main protection function
Protection for all types of faults in systems with earthed, compensated or isolated starpoint
Selectable polygonal tripping characteristic or MHO characteristic
Possibility to choose between Z pickup, I>-, U/I- or U/I/ϕ pickup, enabling the adaptation to different system
conditions and the user philosophies
Reliable differentiation between load and fault conditions also on long, high-load lines
High sensitivity in the case of a lightly loaded system, extreme stability against load jumps and power swings
Optimum adaptation to the line parameters by means of the tripping characteristic with diverse configuration
parameters and „load trapezoid“ (elimination of the possible load impedances)
Six measuring systems for each distance zone
Six distance zones, selectable in forward or reverse direction or non-directional, one can be graded as an
overreach zone
Nine time stages for the distance zones
Direction determination (with polygon) or polarization (with MHO characteristic) is done with unfaulted loop
voltages and voltage memory, thereby achieving unlimited directional sensitivity not affected by capacitive
voltage transformer transients
Suitable for lines with serial compensation
Insensitive to current transformer saturation
Compensation of the influence of parallel line is possible
Shortest command time significantly less than one cycle
Phase-selective tripping (in conjunction with single-pole or single- and three-pole auto-reclosure) possible
Instantaneous tripping following switching onto a fault is possible
Two setting pairs for earth impedance compensation
Power Swing Supplement (optional)
Power swing detection with dZ/dt measurement from three measuring systems
Power swing detection up to 10 Hz swing frequency
Remains in service also during single-pole dead times
settable power swing programs
prevention of undesired tripping by the distance protection during power swings
Tripping for out-of-step conditions can be configured

Table of Contents

Related product manuals