Introduction
1.3 Characteristics
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
30
Teleprotection Supplement (optional)
Different schemes which may be set:
Transfer trip (direct, via pickup or a separately settable overreach zone)
Comparison schemes (permissible overreach transfer trip = POTT or blocking schemes with separate over-
reach zone or directional pickup)
Pilot wire comparison/reverse interlocking (with direct current for local connections or extremely short lines)
suitable for lines with two or three ends
Phase segregated transmission possible in lines with two ends
Signal exchange between the devices via binary outputs and binary inputs, either directly via the device con-
tacts or via the protection data interface(s)
Earth Fault Protection (optional)
Time overcurrent protection with a maximum of three definite time stages (DT) and one inverse time stage
(IDMT) for high resistance earth faults in earthed systems
For inverse-time overcurrent protection a selection from various characteristics based on several standards
is possible
The inverse time stage can also be set as fourth definite time stage
High sensitivity (from 3 mA on, depending on the version)
Phase current restraint against error currents during current transformer saturation
Second harmonic inrush restraint
Optional earth fault protection with voltage-dependent tripping time or with zero sequence power inverse
time tripping
Each stage can be set to be non-directional or directional in forward or reverse direction
Single-pole tripping enabled by integrated phase selector
Direction determination with automatic selection of the larger of zero sequence voltage or negative se-
quence voltage (U
0
, I
Y
or U
2
), with zero sequence system quantities (I
0
, U
0
), with zero sequence current and
transformer starpoint current (I
0
, I
Y
), with negative sequence system quantities (I
2
, U
2
) or with zero sequence
power (3I
0
· 3U
0
)
One or more stages may function in conjunction with a teleprotection scheme; also suited for lines with three
ends
Instantaneous tripping by any stage when switching onto a fault
Sensitive Earth Fault Detection (optional)
for compensated or isolated networks
Detection of the displacement voltage
Determination of grounded phase
Sensitive earth fault directional determination
Angle error correction for current transformers