Introduction
1.3 Characteristics
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
31
Restricted earth fault protection
Earth fault protection for earthed transformer windings
Short tripping time
High sensitivity for earth faults
High stability against external earth faults using the magnitude and phase relationship of through-flowing
earth current
Tripping at Line Ends with no or Weak Infeed (optional)
Possible in conjunction with teleprotection schemes
Allows fast tripping at both line ends, even if there is no or only weak infeed available at one line end
Phase segregated tripping and single-pole automatic reclosure is possible (version with single-phase trip-
ping)
External Direct and Remote Tripping
Tripping at the local line end from an external device via a binary input
Tripping of the remote line end by internal protection functions or an external device via a binary input (with
teleprotection)
Transmission of information
Transmission of the measured values from all ends of the protected object with the magnitude and phase
Transmission of up to 4 fast commands to all remote ends (order option)
Transmission of up to 24 additional binary signals to all remote ends (order option)
Time Overcurrent Protection
Selectable as emergency function during a failure of the main protection function(s) due to a failure of the
data communication and/or the measuring voltages, or as backup function
Maximally three definite time stages (DT) and one inverse time stage (IDMT), each for phase currents and
for earth currents
For inverse-time overcurrent protection a selection from various characteristics based on several standards
is possible
Blocking capability e.g. for reverse interlocking with any stage;
Instantaneous tripping by any stage when switching onto a fault
End fault protection: fast tripping on faults between the current transformer and line isolator (when the iso-
lator switching status feed back is available); particularly well suited to substations with
1
/
2
circuit breaker
arrangements
High Current Switch-onto-Fault Protection
Fast tripping for all faults on 100 % line length
Selectable for manual closure or following each closure of the circuit breaker
With integrated line energization detection.