51 Device is Operational and Pro-
tecting (Device OK)
Device OUT on
off
* * LED BO 135 81 1 Yes
52 At Least 1 Protection Funct. is
Active (ProtActive)
Device IntSP on
off
* * LED BO 192 18 1 Yes
55 Reset Device (Reset Device) Device OUT * * * LED BO 192 4 1 No
56 Initial Start of Device (Initial Start) Device OUT on * * LED BO 192 5 1 No
60 Reset LED (Reset LED) Device OUT_
Ev
on * * LED BO
67 Resume (Resume) Device OUT on * * LED BO 135 97 1 No
68 Clock Synchronization Error
(Clock SyncError)
Device OUT on
off
**LEDBO
69 Daylight Saving Time (DayLight-
SavTime)
Device OUT on
off
**LEDBO
70 Setting calculation is running
(Settings Calc.)
Device OUT on
off
* * LED BO 192 22 1 Yes
71 Settings Check (Settings Check) Device OUT * * * LED BO
72 Level-2 change (Level-2 change) Device OUT on
off
**LEDBO
73 Local setting change (Local
change)
Device OUT * *
110 Event lost (Event Lost) Device OUT_
Ev
on * * LED BO 135 130 1 No
113 Flag Lost (Flag Lost) Device OUT on * m LED BO 135 136 1 Yes
125 Chatter ON (Chatter ON) Device OUT on
off
* * LED BO 135 145 1 Yes
126 Protection ON/OFF (via system
port) (ProtON/OFF)
Device IntSP on
off
**LEDBO
127 Auto Reclose ON/OFF (via
system port) (AR ON/OFF)
Auto Reclose IntSP on
off
**LEDBO
128 Teleprot. ON/OFF (via system
port) (TelepONoff)
Device IntSP on
off
**LEDBO
130 Load angle Phi(PQ Positive se-
quence) (Ï•(PQ Pos. Seq.))
Measurem.Superv OUT * * * LED BO
131 Load angle Phi(PQ) blocked
(Ï•(PQ Pos) block)
Measurem.Superv OUT * * * LED BO
132 Setting error: |PhiA - PhiB| < 3° (ϕ
Set wrong)
Measurem.Superv OUT * * * LED BO
140 Error with a summary alarm
(Error Sum Alarm)
Device OUT on
off
* * LED BO 192 47 1 Yes
144 Error 5V (Error 5V) Device OUT on
off
* * LED BO 135 164 1 Yes
160 Alarm Summary Event (Alarm
Sum Event)
Device OUT * * * LED BO 192 46 1 Yes
161 Failure: General Current Supervi-
sion (Fail I Superv.)
Measurem.Superv OUT * * * LED BO 192 32 1 Yes
163 Failure: Current Balance (Fail I
balance)
Measurem.Superv OUT on
off
* * LED BO 135 183 1 Yes
164 Failure: General Voltage Supervi-
sion (Fail U Superv.)
Measurem.Superv OUT * * * LED BO 192 33 1 Yes
165 Failure: Voltage summation
Phase-Earth (Fail Σ U Ph-E)
Measurem.Superv OUT on
off
* * LED BO 135 184 1 Yes
167 Failure: Voltage Balance (Fail U
balance)
Measurem.Superv OUT on
off
* * LED BO 135 186 1 Yes
168 Failure: Voltage absent (Fail U
absent)
Measurem.Superv OUT on
off
* * LED BO 135 187 1 Yes
No. Description Function Type
of In-
for-
matio
n
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interrogation