Appendix
A.8 Information List
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
738
5811 Restricted earth fault is switched
OFF (REF OFF)
REF OUT on
off
**LEDBO76111Yes
5812 Restricted earth fault is
BLOCKED (REF BLOCKED)
REF OUT on
off
on off * LED BO 76 12 1 Yes
5813 Restricted earth fault is ACTIVE
(REF ACTIVE)
REF OUT on
off
**LEDBO76131Yes
5816 Restr. earth flt.: Time delay
started (REF T start)
REF OUT * on off * LED BO 76 16 2 Yes
5817 Restr. earth flt.: picked up (REF
picked up)
REF OUT * on off m LED BO 76 17 2 Yes
5821 Restr. earth flt.: TRIP (REF TRIP) REF OUT * on m LED BO 76 21 2 No
5826 REF: Value D at trip (without
Tdelay) (REF D:)
REF VI * on off 76 26 4 No
5827 REF: Value S at trip (without
Tdelay) (REF S:)
REF VI * on off 76 27 4 No
6854 >Trip circuit superv. 1: Trip Relay
(>TripC1 TripRel)
TripCirc.Superv SP on
off
**LEDBIBO
6855 >Trip circuit superv. 1: Breaker
Relay (>TripC1 Bkr.Rel)
TripCirc.Superv SP on
off
**LEDBIBO
6856 >Trip circuit superv. 2: Trip Relay
(>TripC2 TripRel)
TripCirc.Superv SP on
off
**LEDBIBO
6857 >Trip circuit superv. 2: Breaker
Relay (>TripC2 Bkr.Rel)
TripCirc.Superv SP on
off
**LEDBIBO
6858 >Trip circuit superv. 3: Trip Relay
(>TripC3 TripRel)
TripCirc.Superv SP on
off
**LEDBIBO
6859 >Trip circuit superv. 3: Breaker
Relay (>TripC3 Bkr.Rel)
TripCirc.Superv SP on
off
**LEDBIBO
6861 Trip circuit supervision OFF
(TripC OFF)
TripCirc.Superv OUT on
off
* * LED BO 170 53 1 Yes
6865 Failure Trip Circuit (FAIL: Trip cir.) TripCirc.Superv OUT on
off
* * LED BO 192 36 1 Yes
6866 TripC1 blocked: Binary input is
not set (TripC1 ProgFAIL)
TripCirc.Superv OUT on
off
**LEDBO
6867 TripC2 blocked: Binary input is
not set (TripC2 ProgFAIL)
TripCirc.Superv OUT on
off
**LEDBO
6868 TripC3 blocked: Binary input is
not set (TripC3 ProgFAIL)
TripCirc.Superv OUT on
off
**LEDBO
7104 >BLOCK Backup OverCurrent
I>> (>BLOCK O/C I>>)
Back-Up O/C SP on
off
**LEDBIBO6441Yes
7105 >BLOCK Backup OverCurrent I>
(>BLOCK O/C I>)
Back-Up O/C SP on
off
**LEDBIBO6451Yes
7106 >BLOCK Backup OverCurrent Ip
(>BLOCK O/C Ip)
Back-Up O/C SP on
off
**LEDBIBO6461Yes
7107 >BLOCK Backup OverCurrent
Ie>> (>BLOCK O/C Ie>>)
Back-Up O/C SP on
off
**LEDBIBO6471Yes
7108 >BLOCK Backup OverCurrent
Ie> (>BLOCK O/C Ie>)
Back-Up O/C SP on
off
**LEDBIBO6481Yes
7109 >BLOCK Backup OverCurrent
Iep (>BLOCK O/C Iep)
Back-Up O/C SP on
off
**LEDBIBO6491Yes
7110 >Backup OverCurrent Instanta-
neousTrip (>O/C InstTRIP)
Back-Up O/C SP on
off
on off * LED BI BO 64 10 1 Yes
7130 >BLOCK I-STUB (>BLOCK I-
STUB)
Back-Up O/C SP on
off
**LEDBIBO64301Yes
7131 >Enable I-STUB-Bus function (>I-
STUB ENABLE)
Back-Up O/C SP on
off
on off * LED BI BO 64 31 1 Yes
No. Description Function Type
of In-
for-
matio
n
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interrogation

Table of Contents