10
Siemens
A6V12681517_enUS_a
Smart Infrastructure
02/09/2023
Power supply
Operating voltage
SSC161.05U,
SSC161.35U
AC 24 V (± 15 %) or DC 24 V (± 20 %)
SSC131.39U
AC 24 V (± 20 %)
Frequency
50/60 Hz
Power consumption
SSC161.05U
Normal Operation: 3.5 VA (AC); 1.5 W (DC)
Peak (Ultra cap recharge): N/A
SSC161.35U
Normal Operation: 3.5 VA (AC); 1.5 W (DC)
Peak (Ultra cap recharge): 8 VA (AC); 4 W (DC)
SSC131.39U
Normal Operation: 3 VA (AC); 1.5 W (DC)
Peak (Ultra cap recharge): 6 VA (AC); 4 W (DC)
Primary fuse or breaker rating
External, 2 A quick blow
Signal input
Control signal
Modulating: DC 0...10 V to Y
Floating: AC 24 V to Y1 or Y2
Input impedance
100 kOhm
Parallel operation (number of actuators)
Max. 10 modulating or 24 floating actuators
1)
Signal output
Feedback signal (modulating actuators only)
DC 0...10 V
Max. output current
1 mA
Max. output voltage
-
Resolution
1:100
Operating data
Position with de-energized contact Y
See "Technical design [ 2]"
Running speed (time for 5.5 mm)
SSC161.05U, SSC161.35U: 5 s/mm ± 25 % (27.5 s ±
25 %)
SSC131.39U: 16 s/mm ± 25 % (88 s ± 25 %)
Positioning force
67 lbf (300 N )
Stroke
0.05" to 0.25" inch (1.2…6.5 mm )
Permissible temperature of medium in the connected
valve
34 to 248°F (1…120)