2
Siemens
A6V12681517_enUS_a
Smart Infrastructure
02/09/2023
NOTICE
SSC131.39U floating fail-safe actuators cannot be run in parallel with legacy SSC81.5U
actuators.
For parallel operation of floating fail-safe SSC actuators all actuators in parallel must be
the same part number.
Voltage at Y1:
Stem extends
Normally open valve
closes, normally closed
valve opens
Voltage at Y2:
Stem retracts
Normally open valve
opens, normally closed
valve closes
No voltage at Y1 or Y2:
Actuator maintains its current position
Voltage applied to both Y1
and Y2 (not recommended):
When no power is supplied, the
SSC131.39U actuator fails with
the stem fully retracted.
Stem moves to Y2