DC 0...10 V control signal
● The valve opens / closes in proportion to the
control signal at Y.
● At DC 0 V, actuator stem is retracted, the normally
closed valve is fully closed and the normally open
valve is fully open.
● When no power is supplied, the SSC161.05U
actuator maintains its current position and the
SSC161.35U actuator fails with the stem fully
retracted.
● This actuator provides a DC 0…10 V position
feedback signal proportional to the stroke of the
actuator stem.
Y = Control signal Y [V]
H = Percentage of calibrated valve stroke
SSC161.05U, SSC161.35U, SSC131.39U
Modulation: Stem
retracting
Flashing green in sequence: LED1-->LED2-->LED3 (500 ms each)
Modulation: Stem
extending
Flashing green in sequence: LED3-->LED2-->LED1 (500 ms each)
At H0 - H40: Constant green (LED3)
At H40 - H60: Constant green (LED2)
At H60 - H100: Constant green (LED1)
Flashing red (LED2): 500 ms on, 500 ms off
Flashing green (LED2): 100 ms on, 100 ms off
Flashing green/red alternatively (LED2): Green 500 ms, red 500 ms
Ultra-cap initial
charging*
Constant green & red simultaneously (LED2): Constant orange
* Only available for SSC161.35U, SSC131.39U
Type summary
Ordering
When ordering, specify both type and quantity.