Run-up and switch-off of the 2-speed motor.
Control se
quence
"Switch-on de
lay", "Switch-off delay", min. switch-on time and min. switch-off time
are considered.
Functio
n diagram
0
0
TiOnMin1
TiCst TiRup
TiOffMin TiOnMin1
0
TiRup
TiOnMin2
TiOnMin1
Speed 2
Speed 1
Off
TiRup = Runup time
Key
TiCst = Rundo
wn time
DlyOn = Switch-on delay
DlyOff = Switch-off delay
TiOnMin1 = On time minimum, Step 1
TiOnMin2 = On time minimum, Step 2
TiOffMin = Off time minimum
Lockin
g 2
nd
speed by
outside temperature
You can lock the se
cond speed if the temperature drops below an adjustable
outside temperature value.
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Aggregates > Motor > Motor 1...6 >
Settings
Operating line Range Factory setting
Speed 2 locked (OT-dependent)
50... 250 °C, ---
---
Setting "---" disables this function. The 2
nd
speed is locked if the function is active
and if there is not outside temperature value during operation.
Notes
8.4.4 Twin motor
Use the "Twin motor" to control e.g. a twin pump.
Purpose
In addition to default functi
ons, RMS705B offers special control functions to
optimally control a twin motor:
Special control function
s
Run prio
rity changeover for motor faults, automatic or manual.
Adjustable changeover period for orderly changeover of motors.
110 / 216
Siemens Switching and monitoring device RMS705B CE1P3124en