EasyManua.ls Logo

Siemens Synco 700 RMZ785 - H;C Demand Application Examples

Siemens Synco 700 RMZ785
213 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10.3 H/C demand application examples
10.3.1 Overview
RMS705B as universal device can assume functions or partial functions of a
consumer, primary controller, or generation.
Application
This results in sophisticated configurations and settings of the corresponding
distribution zones via the Communication menu.
The section explains the various applications and the required configuration and
communication settings to transmit H/C demand.
RMS705B can generate or evaluate demand signals for the following applications:
Consumers (Section 10.3.3).
Primary controllers (Sectio
n 10.3.4).
Generation (Section 10.3.5).
Cons
um
ers and primary controllers (Section 10.3.6).
Consum
ers and generation (Section 10.3.7).
The followi
ng examples ar
e for hot water networks (heat distribution zone).
However, they equally apply to chilled water networks (refrigeration distribution
zone).
Note
10.3.2 Setting rules
Controllers (controllers 1…3, primary controller) on the H/C demand block are
enabled (shown as a cross in the configuration diagrams) if the controller's demand
is to be passed on.
RMS705B as consumer Demand from controllers 1, 2 or 3 is to be passed on (to bus, to digital (d, Q) or
analog (a, Y) output).
RMS705B as primary
controller
Primary controller demand is to be passed on to the bus.
149 / 216
Siemens Switching and monitoring device RMS705B CE1P3124en
Building Technologies H/C demand, H/C changeover 01.04.2010

Table of Contents

Related product manuals