Siemens Synco 700 RMZ785 - Function Check; Wiring Test

Siemens Synco 700 RMZ785
213 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Main menu > Commissioning > Settings > .... or
Setting values
Main menu > Settings > Faults > Fault relay 1…2 >
Operating line Range Factory setting
Fault priority Urgent, Not urgent, All All
Indication of fault Fault internally (optically), Fault
internally (audibly), Fault via bus
(audibly) **
Fault internally
(audibly) *
Inversion Yes, No No
* Factory setting for "Fault relay 2": "Fault via bus (audibly)".
** Max. 1 bus fault message can be processed (even if the priorities are different). Recommendation: Do
not configure 2 bus fault relays.
At menu item "Aggregates", the state of the 2 fault relays can be read.
Display values
Main menu > Aggregates > Faults >
Operating line Current state
Fault relay 1 Off, On
Fault relay 2 Off, On
12.6 Function check / wiring test
During the wiring test, the two fault relays can be enabled directly:
Wiring test
Main menu > Commissioning > Wiring test > Outputs >
Operating line Comment
Fault relay 1 Off, On
Fault relay 2 Off, On
181 / 216
Siemens Switching and monitoring device RMS705B CE1P3124en
Building Technologies Faults 01.04.2010