Siemens Switching and monitoring device RMS705B CE1P3124en
Building Technologies H/C demand, H/C changeover 01.04.2010
10.3.6 Consumer and primary controller
RMS705B contains a consumer side controller (controller 1) and a primary
controller (controller 2). All requests from this heat distribution zone are acquired
and evaluated (i.e. from own controller 1 and other consumers on the bus).
Controller 2 may not be checked as consumer, as these demand signals were
already sent to the "Heat distr zone source side".
Plant Configuration diagram
T
N.Y2
N.Y1
N.X1
N.X2
Consumer
Primary controller
N.X1
°C
N.Y1 N.Y2
N.X2
°C
N.Q1
A B
Heat distr zone 1
Contrl.
Heat distr zone 2
source side
Modul. output
Modul. output
Main menu > Commissioning > Communication > Distribution zones >
Operating line Range Setting
Heat distribution zone 1…31 1
Heat distr zone source side ----, 1…31 2
Setpoint shift on primary controller/controller 2 can be set as "dependent on outside
temperature" rather than demand-dependent.
Example
Communication settings
Note