EasyManua.ls Logo

Siemens Synco 700 RMZ785 - Page 122

Siemens Synco 700 RMZ785
213 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8.4.16 Wiring test
During the wiring test, the motors can be directly switched via the control switch.
Main menu > Commissioning > Wiring test > Outputs >
Wiring test
Operating lin
e Comment
Motor 1…
Motor 6
Off, Speed 1, Speed 2
(2-speed motor on display).
[Motor 1] A…
[Motor 6] A
Off, On
(1-speed motor, twin motor on display).
[Motor 1] B…
[Motor 6] B
Off, On
(twin motor on display).
Adjustable times acting directly on the relay are effective (run-up time, coasting
time).
Note
8.4.17 Assign texts
Adapt the texts for the motors via operation. They are displayed at the relevant
operating line and on the menu.
Main menu > Commissioning > Settings > .... or
Setting values
Main menu > Settings > Aggregates > Motor > Motor 1...6 >
Operating line Range Factory setting
Motor 1…
Motor 6
Max. 20 characters Motor 1…
Motor 6
See Section 16.4 "Editable texts RMS705B" for an overview of all editable texts
and on how to
reset them.
8.4.18 Operating hours
The total number of operating hours is acquired for each motor output. The counter
counts to max. 99 999 hours and then rolls over to 0.
Main menu > Aggregates > Motor > Motor 1...6 >
Display values
Operating ho
urs motor A
0...99'999 h
Operating hours motor B 0...99'999 h
You can adapt the counter value at the password level, and e.g. reset it to 0.
Main menu > Settings > Aggregates > Motor > Motor 1...6 >
Setting values
Operating line Range Factory setting
Operating hours motor A 0...99'999 h 0
Operating hours motor B 0...99'999 h 0
The operating hours for speeds 1 and 2 are summarized for the 2-speed motor
(sum of 1 and 2).
Note
123 / 216
Siemens Switching and monitoring device RMS705B CE1P3124en
Building Technologies Aggregates 01.04.2010

Table of Contents

Related product manuals