9.3.3 Assign texts
You can assign a specific text to each "Signal doubler-inverter". This text is
displayed as menu and operating line text on the operating pages.
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Signal converter > Signal doubler-inverter >
Operating line Range Factory setting
Signal doubler-inverter Max. 20
characters
Signal doubler-inverter
Setting values
See Section 16.4 "Editable texts RMS705B" for an overview of all editable texts
and on how to
reset them.
9.3.4 Function check / wiring test
The current state (inputs/outputs) of the signal doubler inverter is displayed on the
operator unit.
Main menu > Signal converter > Signal doubler-inverter >
Display values
Operating lin
e Comment
Preselection external* %, °C, ----
Modulating output A 0...100 %
Modulating output B 0...100 %
* Dependent on the input identifier.
You can directly control "Signal doubler-inverter" during the wiring test.
Main menu > Commissioning > Wiring test > Outputs >
Wiring test
Operating line Com
ment
Split-Inv output A ----, 0...100 %
Split-Inv output B ----, 0...100 %
136 / 216
Siemens Switching and monitoring device RMS705B CE1P3124en
Building Technologies Signal converter 01.04.2010