11.3.3 Setting values for universal shift
Main menu > Commissioning > Settings > …or
Setting values
Main menu > Settings > Controller 1...3 > Setpoint effects >
Operating line Range Factory setting *
[Setp compensation 2] delta
0.0 K
[Setp compensation 2] end 30.0 °C
[Setp compensation 2] start 20.0 °C
[Setp compensation 1] start 0.0 °C
[Setp compensation 1] end 0.0 °C
[Setp compensation 1] delta
0.0 K
* Depends on analog value; here, e.g. temperature °C.
11.3.4 Troubleshooting
A check is made to see if a sensor is connected to the input when exiting the
commissioning menu.
If the sensor is connected but missing later, a fault message "[…] Sensor error
X.." is generated.
If there is no limitation sensor, limitation is disabled.
171 / 216
Siemens Switching and monitoring device RMS705B CE1P3124en
Building Technologies Universal controller 01.04.2010