Average temperature measurement with 4 passive sensors using LG-Ni1000
sensing element.
Example 3
Main menu > Commissioning > Extra configuration > Input identifier >
Input configuration
Operating line Setting
N.X1 °C
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Inputs > ...X...
Setting values
Operating line Setting
Type Ni1000
Connection di
agram
G
G
G0
X...
M
G0
B...
N
3123A08
AC 24 V
BM
LG-Ni 1000
BM
LG-Ni 1000
B... B...
BM
LG-Ni 1000
BM
LG-Ni 1000
B...
B… Passive sensor
5.2.6 Troubleshooting
When you exit the "Commissioning" menu, a check is made to see which sensors
are connected. Message "[...X...] sensor error" is displayed if one of the sensors
connected at this point is missing later on or if there is a short-circuit.
If there is no measured value due to an open-circuit, the display reads: ----
If there is no measured value due to a short-circuit, the display reads:oooo
No. Text Effect
101…
264
[N.X1] sensor error …
RMZ788(2).X4 sensor error
Non-urgent message; must not be
acknowledged.
Fault messa
g
es