5.3.2 Texts for logical states 0 and 1
A free text can be assigned to each digital input for logical states 0 and 1 (e.g.
On/Off, full/empty, etc.). The text is displayed after it is assigned to the
corresponding input.
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Inputs > ...X...
Setting values
Operating line Range Factory setting
Text for: Logic 0 Max. 20 characters 0
Text for: Logic 1 Max. 20 characters 1
5.3.3 Connection example
Potential-free contacts can be connected to the digital inputs.
Main menu > Commissioning > Extra configuration > Input identifier >
Input configuration
Operating line Setting
N.X2 Digital
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Inputs > ...X...
Setting values
Operating line Setting
Normal position Open
G
G
G0
X...
G0
N
3123A09
AC 24 V
M
F...
p
X... M
F...
Connection di
agram
F… Detector with potential-free switching contact.
36 / 216
Siemens Switching and monitoring device RMS705B CE1P3124en
Building Technologies Inputs 01.04.2010