6.5.2 Limits for output and user-defined unit
The calculated output signal of the modulating output (Y) can be limited high and
low.
In addition, you can assign a user-defined unit.
The output result's unit (K, kW, etc.) is entered as characters and displayed
together with the output value.
Main menu > Commissioning > Settings > … or
Setting
Main menu > Settings > Data acquisition > Calculator > Calculator 1…2 >
Operating line Range Factory setting
Unit Max. 20 characters
Value low -50…9999 0
Value high -50…9999 100
Value low and Value high only limit the DC 0…10 V signal run to the Y-output.
10 V
0 %
0 V
3124D013124D01en
Value low Value high
6.5.3 Assign texts
A specific text can be assigned to each calculator.
Main menu > Commissioning > Settings > … or
Main menu > Settings > Data acquisition > Calculator > Calculator 1…2 >
Free text
Operating line Range Factory setting
Calculator 1…2 Max. 20 characters Calculator 1…2
See Section 16.4 "Editable texts RMS705B" for an overview of all editable texts
and on how to
reset them.
58 / 216
Siemens Switching and monitoring device RMS705B CE1P3124en
Building Technologies Data acquisition 01.04.2010