8.3.1 Activate block
Activate the rotary step switch by assigning command or load to output A.
Do this via the motor block to be connected, the logic block or the continuous
output, i.e. from their configuration menus.
See the following example:
Command
of output A is to act on Logic block 1.
Example
Main menu > Commissioning > Extra configuration > Aggregates > Logic functions > Logic
1...10 >
Config
uratio
n
Operating lin
e Setting (exa
m
ple)
[Logic A] input 1 [Rot step swi 1A] command
Note the following for output switching:
Configure the outputs without gap (order A,B,C,D).
Assign the smallest load to command A in the event of different loads.
Use the type ("Linear", "Flexible", "Binary") to set the step switch properties.
Main menu > Commissioning > Extra configuration > Aggregates > Rotary step switch >
Rotary step switch 1…2 >
Configuration
Operating lin
e Range Factor
y setting
Type Linear, Flexible, Binary Linear
79 / 216
Siemens Switching and monitoring device RMS705B CE1P3124en
Building Technologies Aggregates 01.04.2010