EasyManua.ls Logo

Siemens UL 489 - Page 112

Siemens UL 489
352 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9 – 10
Protective function has tripped
(overcurrent)
- Indicator lights up when the Query
button is pressed
- Only one trip cause is displayed
- Only the last trip cause is
displayed
or
LED T.U. ERROR
1. T.U. Error flashes:
Limited protective function, the protective
parameters are reset to minimum values.
Causes:
- Rated current of the Rating Plug is higher
than that of the circuit breaker
- Rotary coding switch in undefined
intermediate position
- Trip unit defective
2. T.U. Error lights up continuously:
Protective function not available.
Causes:
- Rating Plug not compatible with
circuit breaker type
- Trip unit defective

Table of Contents

Related product manuals