18 – 5
18.2 Truck Operated Contacts - TOC (Cradle Accessory)
Truck-operated contacts (TOC) can be installed in the cradle. These enable the signaling of the horizontal position of the breaker in
the cradle.
(1) TOC signaling switch module
Three versions are available (Order numbers (page 18-7).
WLGSGSW111 (Version 1):
- One form C contact for DISCONNECT position (S30)
- One form C contact for TEST position (S31)
- One form C contact for CONNECT position (S34)
WLGSGSW321 (Version 2):
- One form C contact for DISCONNECT position (S30)
- Two form C contacts for TEST position (S31 and S32)
- Three form C contacts for CONNECT position (S33, S34, and S35)
WLGSGSW6 (Version 3):
- Six form C contacts for CONNECT position (S30, S31, S32, S33, S34, and S35)
Terminals
The TOC accessory is equipped with an integrated terminal block. The integrated terminal block is of spring clamp design, and will accept
1xAWG 20 – 1xAWG 14 for each point
DANGER
Hazardous voltage.
Will cause death, serious personal injury, or equipment damage.
Turn off and lock out all power supplying this equipment before working on this device.