10 – 5
10.4 Installing the remote Bell Alarm reset
10.4.1 Mounting remote reset coil and cut-off switch
- OPEN the circuit breaker and discharge the closing spring (page 24-2).
- Move the circuit breaker into the withdrawn position in the cradle (page 24-3).
- Remove front panel (page 24-4).
- Remove the trip unit (page 9-49).
NOTICE
Can only be used with automatic reclosing lockout reset.
The remote reset coil will otherwise be overloaded and damaged.
DANGER
Hazardous voltage.
Will cause death, serious personal injury, or equipment damage.
Turn off and lock out all power supplying this equipment before working on this device.
WARNING
High speed moving parts.
Can cause serious personal injury.
Discharge the closing spring before inspection and before carrying out any work on the circuit breaker.