24 – 11
24.6 Exchanging the primary disconnects
(1) Finger cluster
(2) Stab tip
24.6.1 Exchanging the finger cluster
- OPEN the circuit breaker and discharge the closing spring (page 24-2)
- Remove the circuit breaker from the cradle (page 24-3)
All frame sizes
1...4 Remove M4 collar screws
5 Remove finger cluster
6 Assemble new finger cluster
7...10 Assemble M4 collar screws
DANGER
Hazardous voltage.
Will cause death, serious personal injury, or equipment damage.
Turn off and lock out all power supplying this equipment before working on this device.
PZ 2
3,2 Nm
28 lb-in
5
4
2
1
3
6
7
8
10
9
(1)
PZ 2
(1) Self-tapping M4 collar screw