10.2 Resetting the Bell Alarm with reclosing lockout (optional)
WL circuit breakers are normally configured to be immediately "Ready-to-close" again following a trip. With the automatic reset of the Bell
Alarm, the tripping coil is automatic resetting after the trip unit has tripped. The circuit breaker is immediately "Ready-to-close" again. For
confirmation, the tripped indicator must be reset, either manually on the trip unit or via the remote reset coil.
When the WL breaker is configured with option WLNOAUTRSET, the tripping coil must be manually reset before the circuit breaker is
capable of closing. The following instruction details the resetting of the Bell Alarm, and the tripping coil.
1
Circuit breaker is tripped by the trip unit
2
Indicators
Signals
3
Manual reset
Press Bell Alarm (red pin), until it latches
4
Bell Alarm reset
Tripping coil and Bell Alarm are reset.
5
Indicators
Circuit breaker is "Ready-to-close" again if the closing spring is charged and no interlock is active.
Bell Alarm
Trip
X9.12 X9.14
X9.13
S24
Bell Alarm
F5
Tripping coil
0077-01_u
Reset
X9.12 X9.14
X9.13
S24