13 – 3
13.2 Optional motor disconnect switch on the front panel
Option.
For switching off the motor-operated mechanism control voltage. Supplied pre-assembled with one wire to be soldered .
Installing motor disconnect switch
Connecting motor disconnect switch
- Disconnect the brown wire from the motor-operated mechanism from terminal X5.2.
- Connect wire X5-2 of the disconnect switch S12 to terminal X5.2.
- Solder the brown wire from the motor-operated mechanism to terminal 4 of the disconnect switch S12.
Rocker
S 12
1
2
Solder point