9 – 86
Changing settings
Indicators
Module test
The correct operation of the cmodules can be verified in the test mode. The test mode is started by pushing the "TEST" button
once. All outputs and the associated LEDs are switched off. The color of the DEVICE LED changes from green to yellow.
Testing inputs and outputs
Pushing the "TEST" button several times in quick succession when an LED is on switches the respective input/output on and off alternately.
LED Indication Significance
DEVICE
green Module in operation
yellow Module in test mode
red Module faulty
c
green Connection to cavailable
off No connection to c
All other LEDs
yellow Option set or signal available
off Option not set or no signal available
NOTICE
Unintended operation of the circuit breaker and other devices.
The test circuits of this unit emit real output signals that may cause operation of the circuit breaker and other devices that
may be connected to the associated cmodule.
During the test, the circuit breaker and downstream devices shoud be isolated to prevent unintended device operations.
Pressing the "TEST" Button Reaction
Twice quickly - LED 1 on
- Input/output 1 on
After a pause,
twice quickly
- LED 1 and input/output 1 off, LED 2 on
- Input/output 2 on
After a pause,
twice quickly
- LED 2 and input/output 2 off, LED 3 on
- Input/output 3 on
... ...
After a pause,
twice quickly
- LED 5 and input/output 5 off, LED 6 on
- Input/output 6 on
After a pause, once Input/output 6 off, all LEDs on
Once Test mode starts again, all inputs/outputs and the associated LEDs are off
The value 0.1 is set if the
rotary switch is positioned
3 x 0.5
1/8“
in this segment