27 – 6
WL Circuit Breaker Accessory Ratings
Truck Operated Contacts (TOC)
Contact rating
Alternating current
50/60 Hz
Rated operational voltage 120 V
Rated operational current, continuous 10 A
Rated operational current, making 6 A
Rated operational current, breaking 6 A
Direct current Rated operational voltage 24 V 24 V, 48 V, 125 V 250 V
Rated operational current, continuous 6 A 1 A 1 A
Rated operational current, making 6 A 0.22 A 0.11 A
Rated operational current, breaking 6 A 0.22 A 0.11 A