Overview
15
Building Technologies A6V10257473_b_en_--.doc
Fire Safety & Security Products 01.2010
4.4 FCP1004-E
Fig. 4 FCP1004-E power supply unit
Mark Function Remarks
1 Mains voltage setting Shunt ON = 115VCA, shunt OFF = 230VCA
2 Mains terminal block
3 Mains fuse 4A / 250V
4 System start without mains power Shunt the 2 terminals with a jumper and
remove after system start
5 Temperature sensor for battery charging voltage compensation Do not cover
6 Internal green LED «Mains operation» but visible from the front Not lit if no mains voltage
7 Battery connection
8 XCM1002 main board connection
Security level of terminal blocks 1 and 2: Dangerous voltage
Security level of other terminal blocks: SELV (Safety Extra Low Voltage)