Special functions
72
Building Technologies A6V10257473_b_en_--.doc
Fire Safety & Security Products 01.2010
17 Special functions
The functions described in this chapter must be used only during commissioning
and/or maintenance. It is not allowed to use these functions during normal
operation. The following access code shall not be delivered to the customer.
17.1 Anticipated Silence Sounders
This function makes it possible to stop/start the Sounders during the pre-warning
time.
1. Enable operating access level 2,
2. Press and hold down "Silence buzzer" key (6), then enter the code 2 1 1 2 4 3
on the numeric keypad:
the sounders stop
3. Press the "Silence/Re-sound Sounders" key (5)
the sounders start again
17.2 Anticipated Reset
This function makes it possible to reset the system without having to wait the end
of the programmed flooding time.
1. Enable operating access level 2
2. Press and hold down the « Silence buzzer » key (6), then enter
the code 2 4 4 2 1 3 on the numeric keypad:
"Pre-warning" time ends immediately and the reset can be carried out

Table of Contents

Other manuals for Siemens XC1005-A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens XC1005-A and is the answer not in the manual?

Siemens XC1005-A Specifications

General IconGeneral
BrandSiemens
ModelXC1005-A
CategoryControl Unit
LanguageEnglish

Related product manuals