MDP 101-1
Page 42 05.06.2020
4.2 Function
The safety functions in the DIAS Drive are controlled over two digital inputs.
The following table shows the status that the ENABLE_L and ENABLE_H inputs must
assume to enable normal operation or trigger the safety function.
Input Status
Relay output S3/S4
Description
ENABLE_L
ENABLE_H
Open
Open
When the servo
amplifier is supplied
with 24 V, the inputs
are closed after a
minimum delay 0.4 of
seconds and a
maximum of 1
seconds
Safe status of the drive
system
Low
Low
When the servo
amplifier is supplied
with 24 V, the inputs
are closed after a
minimum delay 0.4 of
seconds and a
maximum of 1
seconds
Single channel safe
status only when using
classic I/O technology
Safe status of the drive
system, when a safe
output is used by a Safe
PLC, also when
ENABLE_L is connected
with „Ext. GND“
Low
Open
Low
High
Open
Drive system ready
If the ENABLE_L and ENABLE_H are changed from any status to the "Drive Ready" status,
the servo amplifier is not immediately enabled. In addition, in the software (K-EN = 1) or the
corresponding bit in the "control word" must be set so that the software "enable" can be set
and the drive therefore switched to the operational mode.