EasyManua.ls Logo

Sime EDEA - Separate Ducts (Ø 50 MM)

Sime EDEA
80 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
33
Load loss accessory Ø 80 mm
Description Code
Load loss (mm H
2O)
Edea 30
Inlet Outlet
90° curve MF 8077450 0,25 0,30
45° curve MF 8077451 0,20 0,20
Horizontal extension W. 1000
mm
8077351 0,20 0,20
Vertical extension W. 1000
mm
8077351 0,20 0,20
Wall terminal 8089501 0,10 0,35
Roof outlet terminal (*) 8091204 1,10 0,15
Duct kit C(10)3
6296550 - -
6296543 - 1,8
Description Code
Load loss (mm H
2O)
Edea 40
Inlet Outlet
90° curve MF 8077450 0,30 0,4
45° curve MF 8077451 0,25 0,25
Horizontal extension W. 1000
mm
8077351 0,25 0,25
Vertical extension W. 1000
mm
8077351 0,25 0,25
Wall terminal 8089501 0,15 0,50
Roof outlet terminal (*) 8091204 1,5 0,2
Duct kit C(10)3 6296543 - 2,8
(*) The losses of the roof outlet terminal at inlet include the
manifold code 8091400.
NOTE:
for the boiler to operate correctly it is necessary that a
minimum distance of 0.50 m of the duct is respected with a
90° inlet curve.
6.12.6 Separate ducts (Ø 50 mm)
The
Edea
boiler is configured for use in Ø 50 mm discharge
flues. To ensure correct boiler operation, parameter PAR31
(long flues) should be set on the basis of the length of the in-
stalled flues, as indicated in the table.
PAR 31
Edea 30
Ø 50 mm outlet Discharge diaphragm
0 1 x 90° elbow + 2 metres leave it mounted
0 1 x 90° elbow + 6 metres remove
2 1 x 90° elbow + 10 metres remove
4 1 x 90° elbow + 14 metres remove
6 1 x 90° elbow + 18 metres remove
8 1 x 90° elbow + 22 metres remove
10 - -
12 - -
PAR 31
Edea 40
Ø 50 mm outlet Discharge diaphragm
0 1 x 90° elbow + 12 metres remove
2 - -
4 - -
6 - -
8 - -
NOTE:
to remove the discharge diaphragm, proceed as illus-
trated in “Fig. 26”.
120
Ø 80
170
170
Ø 80
320
400
125
125
Fig. 28
Example: calculation of the load loss of a
Edea 30
boiler.
Accessories Ø 80 mm
Code
Quantity
Load loss (mm H2O)
Inlet
Outlet
Total
Extension W. 1000 mm
(horizontal)
8077351
9
9 x
0,20
- 1,80
Extension W. 1000 mm
(horizontal)
8077351
9 -
9 x
0,20
1,80
90° curve
8077450
2
2 x
0,25
- 0,50
90° curve
8077450
2 -
2 x
0,30
0,60
Wall terminal
8089501
1 0,10 - 0,10
Wall terminal
8089501
1 - 0,35 0,35
TOTAL 5,15
(installation permitted since the total of the load loss of the
accessories used is less than 15 mmH
2O).

Table of Contents

Related product manuals