EasyManua.ls Logo

Sime EDEA - Page 76

Sime EDEA
80 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
76
Information requirements for boiler space heaters, boiler combination heaters
Model(s): EDEA 40
Condensing boiler: Yes
Low-temperature boiler: Yes
B11 boiler: No
Cogeneration space heater: No Equipped with a supplementary heater: No
Combination heater: Yes
Item Symbol Value Unit Item Symbol Value Unit
Nominal heat output for space heating
P
n
34 kW
Seasonal space heating energy efficiency
ηs 93 %
For boiler space heaters and boiler combination heaters:
useful heat output
For boiler space heaters and boiler combination heaters:
useful efficiency
At nominal heat output and high-
temperature regime
a
P
4
34,1 kW
At nominal heat output and high-
temperature regime (*)
η4 87,9 %
At 30% of nominal heat output and
low-temperature regime
b
P
1
11,3 kW
At 30% of nominal heat output and
low-temperature regime (*)
η1 97,7 %
Auxiliary electricity consumption Other items
At full load el
max
0,063 kW Standby heat loss Pstby 0,115 kW
At part load el
min
0,015 kW Ignition burner power consumption Pign 0 kW
In standby mode PSB 0,006 kW Emissions of nitrogen oxides NOx 34
mg/
kWh
For combination heaters:
Declared load profile
XXL
Water heating energy efficiency
ηwh 86 %
Daily electricity consumption Qelec 0,220 kWh Daily fuel consumption Qfuel 29,034 kWh
Contact details Fonderie Sime S.p.A. Via Garbo 27, 37045 Legnago (VR) ITALIA
a. High-temperature regime means 60°C return temperature at heater inlet and 80°C feed temperature at heater outlet.
b. Low-temperature regime means for condensing boilers 30°C, for low-temperature boilers 37°C and for other heaters 50°C return
temperature.
(*) The yield data have been calculated using the higher heating value.