A-12
4007ES Panel Programmer Manual (579-1167)
Releasing Specific Controls and Indications, Continued
Abort Switch 
Trouble during 
Normal 
Supervisory 
Conditions
6. Click the List tab in the Programmer and right click the list for the abort switches made 
during step 3 and select where used to show all the custom control equations this list is 
referenced in.
Find these equations in the custom control user equations and whenever the abort switches 
list is referenced for status SUPV, change it to ABNORM. For example:
7. Add a HAZNAME - Abort Switch Trouble equation to annunciate troubles from this abort 
switch as shown below when the hazard area is not in alarm. Use the lists you wrote down 
from above as the input lists and the trouble digital pseudo point you created with the Abort 
Active - No Alarm as the output.
8. Add a HAZNAME - Abort Switch Short Circuit equation to annunciate short troubles 
from this abort switch as shown below. Use the abort list you wrote down from above as the 
input lists and the trouble digital pseudo point you created the Abort Switch Short as the 
output.
Continued on next page