9-10
4007ES Panel Programmer Manual (579-1167)
Custom Control, Continued
General
Information
After you enter a name for the floor group, click Next. A dialog appears, with this dialog you
can specify general information about the application.
.
Figure 9-15. Floor Above/Below Data
Specify this information as follows:
• Program #. Use this entry to specify the Custom Control user program in which this
application is to be stored. Three programs are available for user programs.
• Number of Floors. This specifies the total number of floors controlled by the floor
above/below equations.
• Control # of Floors Above. When a fire occurs, this setting determines how many
floors above the fire floor are notified.
• Control # of Floors Below. When a fire occurs, this setting determines how many
floors below the fire floor are notified.
• Type (select all that apply)
- Non-Audio. Select if using non-audio notification appliances
- Smoke. Select this option to control smoke control (damper/AHU) points
Click Next when you are finished.