Custom Control, Continued
Adding Input
Statements
The second step in creating a new Custom Control equation is to add input statements to the
equation. Repeat the steps in this section until all input statements in the equation have been
defined.
1. In the Equations box, position the cursor just to the right of [INPUTS].
Figure 9-10. Positioning the Cursor
2. Click Add. The dialog shown in Figure 9-11 appears.
Figure 9-11. Select Input Opcode Dialog
3. Click on the drop-down list box, select one of the Opcodes, and click Next. Opcodes
available: Select Opcode, Select Input Qualifier, Select Item, Select Point.
4. The next dialogs displayed by the wizard depend on the Opcode you selected in Step 3.
Follow the Wizard’s windows to create input for the equation.
5. The Finish button becomes available when all dialogs related to the input Opcode have
appeared. Click it to finish defining the input statement.