EasyManua.ls Logo

Simplex 4007ES Hybrid - Walktest

Simplex 4007ES Hybrid
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8-8
4007ES Panel Programmer Manual (579-1167)
Viewing, Adding, and Editing Lists, Continued
WalkTest Editing Group Properties
Each WalkTest group includes a set of properties that allow you to control the way in which
points within the group operate.
To edit the properties for a group:
1. Click on the WalkTest tab at the bottom of the List Window.
2. Double click on one of the WalkTest groups to view its properties window. (Alternatively,
you can right click on the group and select Properties from the menu that appears.)
3. Use the guidelines listed below to set the properties for the WalkTest group.
4. After making changes to the WalkTest Group properties, click on the Apply button to apply
the changes and then click on OK to close the window.
Table 8-2. WalkTest Group Property Guidelines
Tab Properties
WalkTest
Setting the properties in this tab affects all WalkTest groups.
Monitor. A check in this box means monitor points are automatically inserted in
Group 1 - Monitor Zones. If you uncheck this box, you can move points from
one group to another. However, at a later point, if you recheck this box, the
points you previously moved to other groups will be moved back to Group 1.
Control. A check in this box means control points (signals/relays) are
automatically inserted in Group 0 - Signals/Relays. If you uncheck this box, you
can move points from one group to another. However, at a later point, if you
recheck this box, the points you previously moved to other groups will be
moved back to Group 1.
On. Allows you to set the duration of each tone within the PNIS code.
Off. Allows you to set the duration of silence between tones of the PNIS code.
Group
Setting the properties in this tab affects only the selected group.
Monitor. A counter that tracks the number of devices in the group.
Control. A counter that tracks the number of devices in the group.
Reset Delay. Allows you to shorten or lengthen the reset time used by the
monitor device. For example, increase the delay in cases where canned smoke
does not clear from a smoke detector quickly enough.
List
Description. Allows you to change the description of the group’s monitor or
control lists. For example, you can change the name of the WalkTest Group 0 -
Signals/Relays to a more descriptive name, if necessary.

Table of Contents

Other manuals for Simplex 4007ES Hybrid

Related product manuals