4-7
4007ES Panel Programmer Manual (579-1167)
System Options
Table 4-6.
Compatible
Alert Tone Value
User Access Level
Configuration
User access levels can be configured on the programmer for display functions to determine
their access level.
Each access level automatically has access to the level below it. For example, a technician
authorized for level 1 is only able to access functions that are tagged as level 1. A technician
with a level 3 authorization level however, has access to functions tagged as levels 1, 2 and 3.
Note: Passcodes can be attributed to user levels 2, 3, and 4 to restrict the access to certain functions. For
more information consult the Passcode Configuration section.
To associate user levels with a display function:
1. Click on the Panel tab and select the Access Levels sub-tab.
2. Double click on the table entry to open its Object Properties window.
3. Select one of four user levels for the display function. Basic display functions, such as
System Reset and Change Time and Date, are usually assigned to user level 1. More
sensitive display functions, such as Remote Download, are typically assigned to user level 2,
3, or 4.
4. Click on OK to confirm the selection.
Table 4-5. Addressable Appliances Preferred Default System Options, Continued
Assigned Candela
Value
Value for Indoor
Appliances
V
alue for Weatherproof,
UL
Value for
Weatherproof,
ULC
15 cd 15 cd 15 cd 20 cd
20 cd 30 cd WP75 cd 20 cd
30 cd 30 cd WP75 cd 30 cd
75 cd 75 cd 75 cd 75 cd
110 cd 110 cd WP185 cd 75 cd
135 cd 135 cd WP185 cd 75 cd
185 cd 185 cd WP185 cd 75 cd
WP75 cd 75 cd WP75 cd 75 cd
WP185 cd 185 cd WP185 cd 75 cd
HARDWARE Device candela jumper setting determines the output.
Assigned Tone
Compatible
Tone for Appliances
Broadband / 520HZ / Slow Whoop / Bell /
Siren / Hi / Lo / Chime / Hardware Specified
Temporal coding and Broadband tone.