4-6
4007ES Panel Programmer Manual (579-1167)
System Options
Table 4-4. Recurring Trouble Filter System Options
General Description: These options stop a recurring trouble event from continuously dialing 
the central station or from generating SafeLINC email events if the programmed criteria are 
met (number of occurrences of that point in the trouble log within the specified elapsed time 
frame).
Option Description
Occurrences
Number of times the point is found in the Trouble log (0=no filtering; default for 
pre-existing jobs upgraded to 12.06). Value is selectable from 0 and 2 to 10. 
By default, it is set to 3.
Elapsed Time
Number of minutes in which the Troubles must be found. Value is selectable 
from 1 to 1440 minutes. By default, it is set to 60.
Table 4-5. Addressable Appliances Preferred Default System Options
General Description: This option allows System Options to be selected for TrueAlert ES 
appliances that can be configured identically or independently through the ES Programmer 
software. 
To use the System Options to configure TrueAlert ES appliances:
• The appliance's jumpers and configuration switches must be set to the correct setting. For 
example, if a specific candela value is selected in the system options, the device should be 
set to FACP. On the other hand, if system option is set to “Hardware”, the candela flag at the 
device should be set to any other position than FACP.
• The appliance's candela and coding type in the power supply's Point Editing tab in the 
programmer must be set to "System Default".
When a specific candela value is selected, that value applies to all compatible appliances that 
have their configuration switches set to FACP*.
When Hardware Specified is selected, it is the appliance's locally configured candela value that 
is used.
Option System Options
Candela • 15 cd
• 20 cd
• 30 cd
• 75 cd
• 110 cd
• 135 cd
• 185 cd
• Weather Proof 75 cd 
• Weather Proof 185 cd
• Hardware 
Specified
*Note: When a specific candela value is selected, a warning window appears to notify the user that in the 
event that an appliance cannot be set to the selected Preferred Default System Option, a 
compatible default value is assigned to the device by the programmer.
For example: If the System Option is set to 20 cd and there is a UL Weatherproof device (that has 
no 20 cd setting), the Programmer assigns a value of WP75 cd to the UL weatherproof device.
Continued on next page
Panel Information and Configuration, Continued