4-3
4007ES Panel Programmer Manual (579-1167)
Service 
Reset
Select Service Reset to allow an operator to reset the system even though 
the device causing the alarm has not restored to normal. 
The typical application for this would be when a malfunctioning initiating 
device (detector or sensor consisting of a base and removable head) causes 
an alarm, but will not reset even though the off-normal condition is no longer 
present. With this option enabled, the head can be removed and the system 
(including the local energy masterbox, if provided) can be reset. Without this 
option enabled, removing the head will cause the system to abort the reset 
because it will not have seen the alarmed point/zone having restored to a 
normal state, and it will not be possible to reset the local energy masterbox. 
The default setting for this option is disabled.
Combined 
Alarm and 
Hardware 
Reset
If checked, pressing the Reset button performs an alarm reset followed by a 
hardware reset. If this option is not selected, an alarm reset is performed if 
there are fire alarms or supervisories in the system. Otherwise, a hardware 
reset is performed. 
Display First 
Alarm
When this option is selected, the display alternates between the summary 
screen (with the number of active alarms, troubles, etc.) and the screen 
showing detailed information on the first alarm received by the system. 
If this option is not selected, the screen indicating the number of alarm 
conditions on the system is displayed.
Non Steady 
Audible Evac
When enabled, this option allows you to select the type of operation for Non 
Steady Audible Evacuation Signals. The term Non Steady Audible Evacuation 
Signal refers to any Notification Appliance capable of sounding a coded 
signal. The default setting for this option is not enabled. Choices are:
• California Code 1. A coding pattern consisting of 12 beats within a 
10 second span of time, followed by a 2 ½ second pause. This sequence 
repeats four times (four rounds) and then terminates (i.e., the total coding 
pattern lasts approximately one minute).
• California Code 3. Same coding pattern as California Code 1, however the 
sequence repeats 12 times (12 rounds) and then terminates (i.e., the total 
coding pattern lasts approximately three minutes). 
• Fast March Time. A coded signal that uses 120 beats per minute. Each 
beat consists of ¼ second pulse on, ¼ second off. Pattern repeats until 
alarm silence.
• March Time. A coded signal that uses 60 beats per minute. Each beat 
consists of ½ second pulse on, ½ second off. Pattern repeats until alarm 
silence.
• Slow March Time. A coded signal that uses 20 beats per minute. Each beat 
consists of 1.5 second pulse on, 1.5 second off. Pattern repeats until alarm 
silence.
• 
Temporal 4
. A CO gas warning that is a repeated sequence of four 
cycles of 100
 msec on with 100 msec off, followed by 5 seconds off.
• Temporal. A three-pulse coding pattern consisting of three ½ second 
pulses, each separated by a ½ second silence. Each three pulse group is 
separated by 1 ½ seconds of silence. Pattern repeats until alarm silence.
• On Steady.
Note: If the coding pattern selected here is not supported by the notification appliance, 
it will be replaced by a default one.
Continued on next page
Table 4-2. General System Options  (Continued)
Option
Description
(“dflt” indicates the default setting)
Panel Information and Configuration, Continued
System Options