7-3
4007ES Panel Programmer Manual (579-1167)
Point Editing for TrueAlert Device, Continued
TrueAlert ES VO
Appliances Point
Editing
Use this device type to edit TrueAlert ES Visual Only (VO) appliances.
The following editing options are available for this appliance:
Table 7-2. TrueAlert ES VO Point Editing Options
Option Description
Custom Label This field can be used to describe the appliance's function, location, or other
descriptive information.
Alternate Label This field is used to enter an alternative description of the appliance.
Style Select the Style that corresponds to the appliance or device you are programming.
• Indoor.
Available candela
options:
System Default. Sets the candela value to the one selected in
the System Option tab.
15 candela
30 candela
75 candela
110 candela
135 candela
185 candela
Hardware. Selecting this option sets the appliance to the setting
indicated on the appliance's configuration switch or jumper.
• Weatherproof UL.
Available candela
options:
System Default. Sets the candela value to the one selected in
the System Option tab.
15 candela
75 candela
WP 75 candela
WP 185 candela
Hardware. Selecting this option sets the appliance to the setting
indicated on the appliance's configuration switch or jumper.
• Weatherproof ULC.
Available candela
options:
System Default. Sets the candela value to the one selected in
the System Option tab.
20 candela
30 candela
75 candela
Hardware. Selecting this option sets the appliance to the setting
indicated on the appliance's configuration switch or jumper.
Operation Select the type of operation the appliance will signal.
General Evac. The strobe is automatically associated with the “ALL VISUAL”
VNAC by default. The “alarm/alert” switch on the device must
be set to "Alarm".
Other When this mode is selected the user is confirming that the
strobe does not have a default assignation to a particular VNAC
and that the VNAC must be specified by the user.
Mounting Select the mounting location of the appliance: wall-mounted or ceiling-mounted.
Candela Select the candela output of the appliance. The selection varies according to the
appliance style.
Note: The "Copy/Paste/ Special Paste" feature can be used to configure multiple devices identically.