7-6
4007ES Panel Programmer Manual (579-1167)
Point Editing for TrueAlert Device, Continued
TrueAlert ES    
VO-LH 
Appliances Point 
Editing
Use this device type to edit TrueAlert ES Visual Only LED Strobe High Candela (VO-LH) 
appliances. The following editing options are available for this appliance:
Table 7-5. TrueAlert ES VO-LH Point Editing Options
Option Description
Custom Label This field is used to describe the appliance's function, location, or other descriptive 
information.
Alternate Label This field is used to enter an alternative description of the appliance.
Style  Select the Style that corresponds to the appliance or device you are programming. 
• Indoor. 
• Weatherproof UL/
ULC. 
Available candela 
options: 
System Default. Selecting this option sets the candela value to 
the one selected in the System Option tab.
110 candela
135 candela
175 candela
Hardware. Selecting this option sets the appliance to the setting 
indicated on the appliance's configuration switch or jumper. 
Operation  Select the type of operation the appliance will signal. 
General Evac.  The strobe is automatically associated with the “ALL VISUAL” 
VNAC by default. The “alarm/alert” switch on the device must 
be set to "Alarm". 
Other  When this mode is selected the user is confirming that the 
strobe does not have a default assignation to a particular VNAC 
and that the VNAC must be specified by the user. 
Mounting Only a wall-mounted appliance is allowed.
Candela  Select the candela output of the appliance. The selection varies according to the 
appliance style. 
Note: The "Copy/Paste/ Special Paste" feature can be used to configure multiple devices identically.