EasyManua.ls Logo

Simplex 4007ES Hybrid - Page 73

Simplex 4007ES Hybrid
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7-17
4007ES Panel Programmer Manual (579-1167)
Point Editing for TrueAlert Device, Continued
TrueAlert Horn
Appliance Point
Editing
Use this device type to edit TrueAlert Horn appliances. The following editing options are
available for this appliance:
Table 7-14. TrueAlert Horn Point Editing Options
Option Description
Custom Label This field can be used to describe the appliance's function, location, or other
descriptive information.
Style Select the Indoor Style
Coding Type Select the Coding Type to set the cadence of the audible signal.
System
Default
This sets the coding to the value determined in the System Option tab.
Temporal A three-pulse coding pattern consisting of three ½ second pulses,
each separated by a ½ second silence. Each three pulse group is
separated by 1 ½ seconds of silence. Pattern repeats until alarm
silence.
March 60 A coded signal that uses 60 beats per minute. Each beat consists of ½
second pulse on, ½ second off. Pattern repeats until alarm silence.
March 120 A coded signal that uses 120 beats per minute. Each beat consists of
¼ second pulse on, ¼ second off. Pattern repeats until alarm silence.
On Steady On steadily.
Volume Set the appliance volume:
High To use this option the appliance's configuration control must be set to
Panel.
Low To use this option the appliance's configuration control must be set to
Panel.
Note: The "Copy/Paste/Special Paste" feature can be used to configure multiple devices identically.