1-2
 
 
Before installing detectors/sensors, make a survey of the area to be covered in accordance with 
information provided in NFPA 72, (an excerpt of which is provided in the “Smoke Detector/ 
Sensor Applications” section below).  For additional information, refer to NFPA 72 and the 
NEMA Guide for Proper Use of System Smoke Detectors. 
 
  Is there human occupancy? 
  Contents to be protected. 
  Type of construction and use. 
  Burning characteristics of contents. 
  Air movement - stratification. 
  Deflections and obstructions. 
  Height of ceilings. 
  Surface conditions of ceilings. 
  Type of ceiling construction. 
  Total area. 
  Vent locations - velocities - dilution. 
 
Each detector/sensor is capable of providing up to 900 square feet (84 square meters) of coverage, 
depending on the following: 
 
  Requirements of local codes. 
  Results of engineering evaluation. 
 
Special Considerations 
Overview 
Special 
Considerations for 
Smoke Detectors 
and Sensors 
Smoke 
Detector/Sensor 
Applications